 4-Wire Ionization Duct Smoke Detector
System Sensor's Innovair DH100ACDCI reduces the spread of smoke through HVAC air handling systems. As an ionization duct detector, it's ultra-responsive to submicron-sized smoke particles typically found near a fire source.
The DH100ACDCI senses smoke in velocities from 500 to 4,000 feet per minute. When smoke is detected, all interconnected Innovairs will initiate their relays. However, to quickly locate the fire source, only the detector sensing smoke will alarm. Two DPDT Form-C relay contacts, connected to auxiliary equipment, can also be configured to prevent the spread of smoke through a particular area. Beyond its reliable performance, the DH100ACDCI is simple to install and maintain. Powered by 24 VAC/DC or 120/240 VAC, it can be easily mounted to round and rectangular ducts, from one to twelve feet in width, with outside mounting tabs. It also offers an adjustable telescopic sampling tube that can be used for duct widths up to 18 inches. The tube locks into place - no additional tools are necessary. Its modular construction allows for easy cleaning and field replacement of the power and sensor boards. Also simplifying maintenance is a transparent cover that provides convenient visual inspection. If the cover is removed, a patented cover-tamper trouble signal gives a 7-minute delay before the panel or remote accessory is notified of trouble. At a remote location, the remote test station option ensures that a detector is functioning properly, and the remote sounder/LED indicator options signal if a detector is in alarm. However, the cover does not need to be removed if a detector needs to be reset at the detector. Simply push the built-in reset button. WARNING: Duct smoke detectors are NOT a substitute for open area smoke detectors, NOT a substitute for early warning detection and NOT a replacement for a building's regular fire detection system. Refer to NFPA 72 and 90A for additional information.
Features
* Ionization technology * An air velocity rating from 500 feet per minute to 4,000 feet per minute (2.54 meters per second to 20.32 meters per second) * Patented interconnectability for multi-fan shutdown * Two DPDT Form-C relay contacts * 24 VAC/DC or 120/240 VAC * Versatile mounting options * Outside mounting tabs * A patented telescopic sampling tube * Modular construction * A patented cover-tamper trouble signal * A transparent cover * A remote test station * Remote sounder/LED indicator options * A built-in reset button
Agency Listings
268A
Innovair Duct Smoke Detector Specifications
Architectural/Engineering Specifications The air duct smoke detector shall be a System Sensor Model DH100ACDCI Series Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The detector shall operate at air velocities of 500 feet per minute to 4000 feet per minute (2.54 to 20.32 meters/ second). The unit shall be capable of controlling up to ten (10) air handling systems when interconnected with other detectors. The detector shall be capable of providing a trouble signal in the event that the front cover is removed. It shall be capable of local testing via magnetic switch or remote testing using the SSK451 Multi-Signaling Accessory or the RTS451KEY Remote Test Station. The unit shall be reset by local reset button or remote test station. The duct smoke detector housing shall incorporate an airtight smoke chamber in compliance with UL 268A, Standard for Smoke Detectors for Duct Applications. The housing shall be capable of mounting to either rectangular or round ducts without adapter brackets. An integral filter system shall be included to reduce dust and residue effects on detector and housing, thereby reducing maintenance and servicing. Sampling tubes shall either be telescoping or be easily installed by passing through the duct housing after the housing is mounted to the duct. The unit shall provide a spacial separation of no less than 1/4 (6.4 mm) and/or a physical barrier between the high and low voltage terminals. The enclosure shall meet all applicable NEC and NFPA standards regarding electrical junction boxes. Terminal connections shall be of the strip and clamp method suitable for 12-18 AWG wiring. Physical Specifications Size 1438 (37 cm.) Length; 51/2 (14 cm.) Width; 23/4 (7 cm.) Depth Shipping Weight 33/4 lbs. (1.7 kg.) Operating Temperature Range 32 to 120F (0 to 49C) Operating Humidity Range 10% to 93% relative humidity non-condensing Air Duct Velocity 500 to 4000 ft./min. (2.54 to 20.32 m/sec.) Electrical Ratings - DH100ACDCLP (Includes Detector) Power supply voltage: 20-29 VDC 24 VAC 50-60 Hz 120 VAC 50-60 Hz 220/240 VAC 50-60 Hz Input capacitance: 270 F max. 270 F max. N/A N/A Reset voltage: 3.0 VDC min. 2.0 VAC min. 10 VAC min. 20 VAC min. Reset time (with RTS451): .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. Reset time (by power down): 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. Power up time: 34 sec. max. 34 sec. max. 34 sec. max. 34 sec. max. Alarm response time: 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. Sensitivity Test: See detector label See detector label See detector label See detector label Current Requirements (Using No Accessories) Max. standby current: 15 mA 35 mA RMS 25 mA RMS 15 mA RMS* Max. alarm current: 70 mA 125 mA RMS 35 mA RMS* 25 mA RMS* Contact Ratings Alarm initiation contacts (SPST): 2.0A @ 30 VAC/DC (0.6 power factor) Alarm auxiliary contacts (DPDT): 10A @ 30 VDC; 10A @ 250 VAC Note: Alarm auxiliary contacts must switch 100mA minimum at 5 VDC. Alarm auxiliary contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose. Trouble contacts (SPDT): 2.0A @ 30 VDC (resistive); 2.0A @ 125 VAC (resistive) Accessory Current Loads at 24 VDC Device Standby Trouble Alarm APA451 12.5 mA Max. n/a 30 mA Max. PA400 0 mA n/a 15 mA Max. RA400Z 0 mA n/a 10 mA Max. RTS451/RTS451KEY 12 mA* n/a 7.5 mA Max. SSK451 5 mA Max. 9 mA Max. 30 mA Max. *Note: When a unit is powered at the 120 VAC or 220/240 VAC input, any combination of accessories may be used such that the given accessory loads are: 60 mA or less in the standby state; 110 mA or less in the alarm state.
A05-0315-002
Wiring Guide
System wiring diagram for 4-wire duct smoke detectors
AVAILABLE POWER INPUTS POWER INPUTS ACCEPT 24 VDC, 24 VAC 50-60 HZ, 120 VAC 50-60 HZ, OR 220/240 VAC 50-60 HZ. CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR. 9 10 A B C 9 AVAILABLE POWER INPUTS 10 A B C CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR. SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPLY INFORMATION.
24V
120 VAC
24V
120 VAC
220/240 VAC ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 18 7 17 6 C. N.O. N.O. C.
220/240 VAC ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 8 N.C. 16 N.C. 6 C. 17 N.O. 7 N.O. 18 C. 8 N.C. FOR WIRING OF AUXILIARY DEVICES, REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER. NOTE: THE SUPERVISORY RELAY NOW PROVIDES A "FORM C" CONTACT FOR CUSTOMIZED APPLICATIONS. FOR STANDARD APPLICATIONS, ONLY THE "NO" CONTACT IS USED
AUX. CONTACT RATINGS 10A @ 30 VDC RESISTIVE 10A @ 250 VAC 100mA MINIMUM @ 5 VDC NOT INTENDED FOR CONNECTION TO CONTROL PANELS.
16 N.C.
ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS. TROUBLE CONTACT RATING 2.0 A @ 30 VDC resistive SUPERVISORY TROUBLE CONTACTS 14 3
ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS. SUPERVISORY TROUBLE CONTACTS 14 3
TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.
TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL.
+
5 ALARM INITIATION LOOP ALARM INITIATION CONTACTS 4 CONTACTS SHOWN OPEN IN STANDBY. CONTACTS CLOSE IN ALARM. ALARM INITIATION CONTACTS 4 5 CONTACTS SHOWN OPEN IN STANDBY. CONTACTS CLOSE IN ALARM.
-
UL LISTED 4-WIRE CONTROL PANEL FIRST DETECTOR IN THE LOOP DH100ACDCI LAST DETECTOR IN THE LOOP DH100ACDCI EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER
Wiring diagram for the DH100ACDCI to RTS451/ RTS451KEY and interconnect feature:
DH100ACDCI Alarm Signal Aux. Power + Sup. N. O. Sup. COM Aux. Power - Reset Test Interconnect - 15 19 14 3 20 2 11 1 2 3 4 5 RTS451/RTS451KEY 1 6 (Red LED) Alarm (Green LED) Power
Wiring diagram for DH100ACDCI to SSK451 and interconnect feature:
FIELD INSTALLED JUMPER FOR TEMPORAL PATTERN COMMON TEMPORAL SELECT ALARM SIGNAL SUPERVISORY SIGNAL RESET TEST POWER (-) POWER (+) 3 2 1 4 7 8 6 5 15 3 14 2 11 20 19 12 1 SSK451 FIELD INSTALLED JUMPER ALARM SIGNAL NO SUPERVISORY CONTACT
Wiring diagram for DH100ACDCI to APA451:
DH100ACDCI Alarm Signal Aux. Power + Sup. N. O. Sup. COM Aux. Power - 15 19 14 3 20 1 Common 3 Power APA451 2 Alarm
*
RESET TEST AUX. POWER (-) AUX. POWER (+) INTERCONNECT + INTERCONNECT - DH100ACDCI UNIT 1
NOTE: Wiring diagram shown is for DH100ACDCI 4-wire duct smoke detector system equipped without a control panel. NOTE: A trouble condition is indicated when the green LED is not illuminated.
12 1
INTERCONNECT + INTERCONNECT - DH100ACDCI UNIT 2
Interconnect + 12 Unit 1 DH100ACDCI UNIT 2 Interconnect - 1
*NOTE: For RTS451KEY only without a Control Panel.
RTS451 does not have a terminal 6.
NOTE: Wiring diagram shown is for DH100ACDCI 4-wire duct smoke detector system equipped without a control panel. NOTE: A trouble condition is indicated when the green LED is not illuminated.
Interconnect + 12
Coil Note: Please note that the magnetic coil supplied with the RTS451/RTS451KEY is not required when these accessories are used with the DH100 detectors. The functionality of the magnetic coil has been designed into the circuitry of the Innovair duct smoke detectors.
*NOTE: For RTS451KEY only without a Control Panel. RTS451 does not have a terminal 6. NOTE: Wiring diagram shown is for DH100ACDCLP 4-wire duct smoke detector system equipped without a control panel. NOTE: A trouble condition is indicated when the green LED is not illuminated.
Important Interconnect Notes
* When using the interconnect feature, all interconnected units must be powered with the same, independent supply. * Polarity must be maintained throughout the interconnect wiring. Connect terminal 12 on unit 1 to terminal 12 on unit 2 and so on. Similarly, connect terminal 1 on unit 1 to terminal 1 on unit 2 and so on.
A05-0315-002
Accessories
System Sensor provides system flexibility with a variety of accessories, including two remote test stations and several different means of visible and audible system annunciation. As with our duct detectors, all duct smoke detector accessories are UL listed.
APA451 Piezo Annunciator (UL S4011)
RTS451KEY Remote Test Station with Key (UL S2522)
PA400W Mini-Alert Sounder (UL S3593) shown with PS24LOW add-on strobe (PS12/24SLENSW smoke lens option available)
RTS451 Remote Test Station (UL S2522)
RA400Z Remote Annunciator (UL S2522)
SSK451 Multi-Signaling Accessory (UL 268A)
SSK451 Multi-Signaling Accessory (UL 268A) shown with PS24LOW add-on strobe (PS12/24SLENSW smoke lens option available)
Ordering Information
Part No. DH100ACDCI A5052 A5064 Accessories ST-1.5 ST-3 ST-5 ST-10 T80-71-00 P48-55-00 SSK451 RTS451KEY RTS451 APA451 Description 4-wire ionization duct smoke detector Replacement ionization detector board Replacement 4-wire power board Metal sampling tube duct widths 1-2 (0.3-0.6 m) Metal sampling tube duct widths 2-4 (0.6-1.2 m) Metal sampling tube duct widths 4-8 (1.2-2.4 m) Metal sampling tube duct widths 8-12 (2.4-3.7 m) Replacement telescoping sampling tube Replacement end cap for T80-71-00 Multi-signaling accessory Remote test station with key lock Remote test station Remote annunciator with piezo alarm MOD400R RA400Z F36-09-11 M02-04-00 P48-21-00 S08-39-01 PA400W PS24LOW PS12/24SLENSW PS12/24SLENSC Sensitivity test module Remote annunciator alarm LED Replacement air filters (two per package) Test magnet End cap for metal sampling tubes Photo replacement screen Mini-Alert sounder Mini-Alert add-on strobe Wall-mount "SMOKE" lens Ceiling-mount "SMOKE" lens
3825 Ohio Avenue * St. Charles, IL 60174 Phone: 800-SENSOR2 * Fax: 630-377-6495
(c)2006 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-0315-002 * 9/06 * #1676


▲Up To Search▲   

 
Price & Availability of DH100ACDCI

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X